Subscribe to follow us via email. Fill in your first and last name, your country and city, your company and your email to receive latest news (daily/weekly/monthly updates), information about new events (seminars, webinars and videos) and notifications about our newest Swegon Air Academy Case Studies straight to your mailbox. Please use English names for your country and city.

Select list(s):


Balancing of a damper-optimised demand controlled ventilation system!
News
February 12, 2015

Balancing of a damper-optimised demand controlled ventilation system!

Balancing of a damper-optimised DCV system consists of the following steps:

  • Control that all the DCV units,room sensors/ room regulators etc. have supply voltage and no polarity error.
  • Program the actual maximum and minimum airflow rates values (Vmax and Vmin) on each DCV damper and set the dampers to automatic mode.
  • If the DCV units do not give the expected response, check the polarity on the supply voltage.
  • Complete the VAV control form. The completed control form should be included in the documentation of the ventilation system.

 DO-DCV

Source from article on “Commissioning for energy-optimal Demand-Controlled Ventilation” by Mads Mysen, Peter G Schild, Axel Cablé and John Woollett